What size wire do you use for 200 amp service?
What is this? For a 200 amp service, you’ll need: #2/0 copper wire, or. #4/0 aluminum or copper-clad aluminum wire.
What copper wire is rated for 200 amps?
SERVICE ENTRANCE CONDUCTORS SIZE AND RATING | ||
---|---|---|
Service or Feeder Rating | Copper Conductors | Aluminum or Copper-Clad Aluminum |
125 Amps | #2 AWG | #1/0 AWG |
150 Amps | #1 AWG | #2/0 AWG |
200 Amps | #2/0 AWG | #4/0 AWG |
What size copper wire do I need for a 200 amp sub panel?
What Size Ground Wire for 200 Amp Service

Size of Main Panel | Copper Conductors | Aluminum or Copper-Clad Aluminum |
---|---|---|
125 Amps | #8 AWG | #6 AWG |
150 Amps | #6 AWG | #4 AWG |
200 Amps | #4 AWG | #2 AWG |
What is the difference between #2 wire and 2 0?
2 AWG will handle around 94 Amps, while 2/0 AWG will handle around 190 Amps. The length of the wire must be considered as well as the % voltage drop in order for this to be true. For a 3% drop where the load is less than 20 feet from the battery and you are drawing 100 Amps, you would need 2/0.
What size copper wire do I need for a 400 amp service?
For a 400 amp service, you will need a 600 kcmil-gauge copper wire.
Can you feed a 200 amp sub panel from a 200 amp main panel?
Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

How many breakers can I put in a 200 amp panel?
How many circuit breakers in a 200 amp panel? Most 200-amp breaker panels have 40 to 42 slots of single-pole breakers or 20 slots for double pole breakers.